Two different jobs
- Running things directly in an outage: the generator powers your appliances. Size it to the loads.
- Backing up a solar system: the generator charges the batteries during a dark week, and the inverter runs the house. Size it to the battery charger.
Running things directly
- Add the running watts of everything that could be on at the same time.
- Find the one appliance with the biggest starting surge, and add the extra it needs to start (its starting watts minus its running watts). Only the biggest one counts, since motors rarely start at the same moment.
- Leave some room: a generator run near its limit all day works hard and burns more fuel.
| Appliance | Running watts | Watts to start |
|---|---|---|
| Refrigerator | 100–250 W | about 1,200 W |
| Chest freezer | 60–100 W | about 800 W |
| Sump pump (⅓–½ hp) | 300–800 W | about 2,000 W |
| Furnace fan | 100–800 W | about 1,200 W |
| Well pump (½–1 hp) | 800–1,500 W | about 3,500 W |
| Window AC | 500–1,000 W | about 2,000 W |
| Microwave | 1,000–1,500 W | about 1,500 W |
| Space heater | 1,500 W on high | about 1,500 W |
Outage examples
Essentials: fridge 250 W, chest freezer 100 W, sump pump 800 W, furnace fan 800 W (an older motor) and lights and chargers 200 W come to about 2,150 W running. The sump pump's start adds about 1,200 W more, so about 3,350 W at the worst moment. A 3,500–5,000 W generator covers it with room to spare.
Essentials plus a well pump: add 1,500 W running, and the pump becomes the biggest starter (about 2,000 W extra). That's about 3,650 W running and 5,650 W at start-up: a 6,000–7,500 W generator, with a 240V outlet if the pump needs it.
Backing up a solar system
Here the generator only has to feed the battery charger (plus whatever runs while it charges), so the charger's rating sets the size:
| System | Charger | Generator |
|---|---|---|
| 12V van or RV, Victron MultiPlus-II 12/3000 | up to 120 A, about 1.7 kW | about 2,000–3,000 W |
| 48V cabin or home, EG4 6000XP | up to 110 A from a generator, about 5.5–6 kW | EG4 recommends more than 10 kW per inverter; or set the generator charge current lower to match a smaller one |
Two details from the manuals worth knowing before you buy:
- Clean power: EG4 asks for a generator with under 3% total harmonic distortion (THD). It's on most inverter generators' spec sheets; check before you buy.
- Turn the charger down to fit: both makers let you lower the charging current (Victron's AC input current limit, EG4's generator charge current setting), so a smaller, quieter generator works; it just charges more slowly.
In a dark-winter area, a small generator for the worst weeks usually costs less than doubling the batteries. Power station vs generator vs solar compares the options for outages, and the home backup guide sizes a battery system that runs the house silently.
Questions people ask
What size generator do I need to run a refrigerator?
A fridge runs at 100–250 W but needs about 1,200 W to start its compressor. Any generator of 2,000 W or more starts it, with room for lights and phone charging.
What size generator for a well pump?
A ½–1 hp well pump runs at 800–1,500 W and can need about 3,500 W to start. With a fridge and lights on too, plan on a generator with at least 5,000 starting watts, and check it has a 240V outlet if your pump is 240V.
What size generator do I need to charge my solar batteries?
Match it to the battery charger, not the battery. A Victron MultiPlus-II 12/3000 charges at up to 120 A, about 1.7 kW, so a 2,000–3,000 W generator suits it. An EG4 6000XP can charge at up to 110 A from a generator; EG4 recommends more than 10 kW per inverter to run loads and charge at once, or set the generator charge current lower to match a smaller one.
Does an off-grid inverter need an inverter generator?
It needs clean power. EG4's 6000XP manual asks for a generator with under 3% total harmonic distortion (THD). Many inverter generators meet that; check the spec sheet of an open-frame one before you buy.
Sources
- Generator wattage chart (running and starting watts) Champion Power Equipment
- EG4 6000XP manual, 6.8: working with a generator (>10 kW per inverter, THD <3%, generator charge current 0–110 A) EG4 Electronics
- EG4 6000XP spec sheet (max AC charge 115 A at 48 V) EG4 Electronics
- MultiPlus-II inverter/charger datasheet (charger current, AC input current limit) Victron Energy
- Estimating appliance and home electronic energy use US Department of Energy
Every number on this page comes from these sources. Spotted something out of date? Tell me.
Get the exact setup
A few taps and you'll know exactly what to buy for your situation.